The PresSura™ Room Pressure Controller Model 8630-PC is designed to maintain a constant pressure differential in hospital rooms.

The 8630-PC measures the actual room pressure differential using TSI's unique bi-directional pressure sensor. It modulates a damper or variable frequency drive to maintain a safe pressure differential. If the pressure differential should rise too high, fall too low, or go to the wrong direction, the Model 8630-PC will activate audible and visual alarms. The 8630-PC even accepts supply and exhaust volumetric flow measurements, alarming if the ventilation rate is too low.

The 8630-PC features adjustable alarm delays to avoid nuisance alarms. When the room is unoccupied, it can be changed to no isolation mode, de-activating all alarms.

The 8630-PC easily integrates to the building management system using a low alarm relay and an analog output of the measured pressure differential, or digital communications over an RS-485 network using the open MODBUS protocol.

Applications

  • Hospital rooms requiring negative pressure

Included Items

  • Digital interface module
  • Through-the-wall pressure sensor
  • Sensor cable, 25 ft
  • Transformer, 120:24 VAC, 25 VA
  • Transformer cable, 25 ft

Features & Benefits

  • Meets ANSI/ASHRAE/ASHE Standard 170-2008, Ventilation of Health Care Facilities
  • Meets The Facility Guidelines Institute (FGI) 2010, Guidelines for Design and Construction of Health Care Facilities
  • Meets Centers for Disease Control (CDC), Guidelines for Environmental Infection Control in Health Care Facilities
  • Meets United States Pharmacopeia (USP), General Chapter <797>, Guidebook to Pharmaceutical Compounding - Sterile Preparations
  • Stand-alone room pressure controller ensures system operation
  • Accepts second pressure sensor input to monitor anteroom differential
  • Direct pressure measurement provides continuous monitoring
  • Audible and visual alarms warn staff of unsafe conditions
  • Convenient keypad and display support local programming
  • Passwords prevent unauthorized access to controller functions